Novaris SFD surge filters provide the highest level of protection for critical and essential equipment up to 6A per phase.
SFD1 - 10 - 13 - 2 : Filter, 1 Phase, 10A, 13kA, 275VRMS BASIC
SFD1 - 10 - 13 - 275 - L: Filter, 1 Phase, 10A, 13kA, 275VRMS BASIC, LED indicator -
SFD1 - 10 - 13 - 275 - A : Filter, 1 Phase, 10A, 13kA, 275VRMS BASIC, Alarm contact and LED indicator -
SFD1 - 10 - 50 - 275 - A : Filter, 1 Phase, 10A, 50kA, 275VRMS BASIC, Alarm Contact & LED indicator
SFD1 - 10 - 50 - 275 - L : Filter, 1 Phase, 10A, 50kA, 275VRMS BASIC, LED indicator -
SFD3 - 10 - 13 - 275 - A: Filter, 3 Phase, 10A, 13kA, 275VRMS BASIC, Alarm Contact & LED indicator -
SFD3 - 10 - 13 - 275 - L : Filter, 3 Phase, 10A, 13kA, 275VRMS BASIC, LED indicator -
SFD3 - 10 - 50 - 275 - A : Filter, 3 Phase, 10A, 50kA, 275VRMS BASIC, Alarm Contact & LED indicator -
SFD3 - 10 - 50 - 275 - L : Filter, 3 Phase, 10A, 50kA, 275VRMS BASIC, LED indicator -
- Giá trên chưa tính thuế VAT 10%.
|
|
SFD1-10 13-275 |
SFD1-10 50-275-A |
SFD3-10 13-275-A |
SFD3-10 50-275-A |
|
| Electrical Specifications |
|
| Connection type |
Series |
|
| Modes of protection |
All mode (L-N, L-PE, N-PE) |
|
| Nominal voltage |
U0 |
230V / 50Hz |
|
| Maximum continuous voltage |
Uc |
275V / 50Hz |
|
| Phases |
1 |
3 |
1 |
3 |
|
| Maximum discharge current (8/20μs) |
Imax |
13kA |
50kA |
13kA |
50kA |
|
| Maximum load curent |
IL |
10A |
|
| Protection stages |
MOV / LC filter / MOV |
|
| Voltage protection level @ 3kA (8/20μs) |
<700V |
|
| Response time |
tA |
Instantaneous |
|
| Earth leakage current |
<500μA |
|
| Maximum voltage drop (% of U0) |
ΔU |
<1%
|
|
| Displays (optional) |
LED power and status |
|
| Alarms (optional) |
Overcurrent / thermal, SPDT contact |
|
| Alarm isolation to active circuitry |
4kV |
|
|
|
|
|
|
|
|
| Mechanical Specifications |
|
|
|
|
|
|
| Operating temperature / humidity |
-40 to +40ºC / 0 to 90% non-condensing |
|